Medium-voltage switchgear maintenance service

Medium-voltage switchgear is an important electrical equipment in the electrical system of tools and factories. Therefore, ensuring the operation of the machine by performing periodic maintenance.

I. Main causes of serious incidents for medium voltage cabinets

  • Room environment
  • Incorrect actions of operators
  • Incorrect way of preserving intermediate cabinets

II. Conditions to ensure the operation of medium voltage cabinets

1. Environmental conditions in the electrical room:

According to the IEC62271-1 standard, the electrical room must ensure the following conditions:

Temperature:

  • Maximum temperature is 40oC
  • Maximum maximum temperature is 35oC in an average of 24 hours
  • Minimum temperature is -5oC

No instruments:

  • No dust, gas, salt, flammable substances, etc.

Humidity:

  • Average humidity 24 hours ≤ 95%, monthly ≤ 90%
  • Average pressure 24 hours ≤ 2.2 kPa, monthly ≤ 1.8 k

2. Operation staff:

  • Learn the technical features, characteristics, and how to use the equipment.
  • Master the operating procedures of each kind of equipment according to technical requirements.
  • Always check, and monitor abnormalities, quality management must be implemented seriously and safely.
  • Operators must have the appropriate capacity and qualifications and must be trained periodically every year.
  • Manage user and vehicle regulations to avoid risks and the entire system.
  • Operators must take the initiative: to ensure safety, ensure quality, emergency response measures, and write and report.

3. Equipment maintenance:

Maintaining the cabinet is not simply cleaning the equipment or applying lubricants to the joints.

  • Clean the equipment
  • Check the equipment by simulating the equipment in operation, using specialized equipment to evaluate the product status.
  • Give suggestion about the equipment replacement that does not meet operating requirements to avoid unwanted incidents.

OTECH with a team of engineers trained and trained annually by manufacturers along with modern equipment brings the best quality in equipment maintenance and repair.

III. OTECH’s central cabinet maintenance service

Our central cabinet maintenance service includes:

1. General inspection:

  • Develop damage to the cabinet and equipment inside the cabinet
  • Vacuum and clean the equipment with specialized services

2. Mechanical testing:

  • Check the operation of closing, cutting the base, and electricity
  • Clean, and apply specialized fire-resistant contact grease

3. Circuit breaker inspection and testing:

  • Check the operation of closing, cutting the base, and electricity
  • Clean, and take care of the next specialized grease at the next machine cutting points
  • Check the return line between phase-phase and phase-shell
  • Check the contact resistance (µohm) between the contact poles of the circuit breaker

4. Busbar inspection and testing:

  • Check, clean, and tighten loose connections
  • Measure the resistance

5. Check the address and the next interlock link:

  • Check the communication line to the ground system connection
  • Check the indication, and interlock between the circuit breaker, disconnector, cabinet, and the ground connection for correct and safe operation.

6. Relay inspection and testing:

  • Check the protection function by supplying a secondary current and simulating the operation
  • Recheck the appropriate input/output connection.
  • Analyze the appropriate settings for downloading

7. Check the current transformer (CT), voltage transformer (VT), and fuses:

  • Check the protection level of CT and VT.
  • Check the resistance value of the secondary, secondary wires.
  • Recheck the demand value.

8. Check the local electrical system before and after maintenance:

We commit that if we detect signs of discharge during the first inspection, and during the maintenance of the central cabinet, we will thoroughly handle the problem and re-measure.

9. Customer benefits when using Otech’s services:

  • Report on the operating status, operation, and aging level of the medium-voltage switchgear
  • Suggest solutions to solve and improve the system status
  • Support for checking parameter settings
  • Free operation training for factory staff
  • 24/7 support, OTECH engineers support solving problems related to the system

– – –

For more information about the medium-voltage switchgear maintenance service, please contact us through the information below:

OTECH JOINT STOCK COMPANY

  • Hotline: 1800 9472
  • Phone number: (+84) 28 6686 3565
  • Email: service@otech.com.vn
  • Address: 02 Street 15, Van Phuc 1 Residential Area, Hiep Binh Phuoc Ward, Thu Duc City, Ho Chi Minh City, Vietnam.
GET IN TOUCH WITH OTECH
Please fill in the information boxes below, OTECH will contact you as soon as possible for a consultant!