Other services
110kV Transformer Station Maintenance Service
Due to the increasing electricity demand, transformer stations are appearing more and more. With the function of increasing voltage to reduce power losses during the transmission of electricity to the point of consumption, this is an indispensable component in the power system.
Among them, the 110 kV transformer station is a transformer station with an installed capacity of 2x 25 MVA, responsible for supplying electricity to an area, it can even supply electricity to an entire district.
During operation, the 110 kV station needs to be periodically maintained to avoid damage, ensure stability, and increase the life of the equipment.
The necessary of 110 kV station maintenance
Because the transformer station operates regularly and continuously, it can be overloaded, leading to damage.
During operation, the 110 kV station needs to be periodically maintained to ensure stability and increase the life of the equipment. This maintenance is carried out periodically according to the published regulations of the product when installed.
Over time, some equipment in the 110kV station may encounter some problems that cause damage. The most obvious signs are broken fuse wires, and power outages in the entire system. The cause of the problem may be due to internal equipment errors or incorrect power usage, or it may be due to natural disasters such as lightning, fire, or animal damage.
Carrying out maintenance of the 110kV transformer station will help minimize damage or serious electrical problems that may occur because the technician will have to check the entire transformer station to see if there are any problems. This helps prevent and limit the dangers caused by the station to people as well as other electrical equipment.
110kV transformer station maintenance process that OTECH provides
We carry out the work comprehensively to bring a transformer station
- 110kV lightning arrester: measure insulation resistance; measure leakage current; check grounding system wires; check connections, wiring; industrial cleaning.
- 110kV/0.11kV voltage transformer: measure insulation resistance; measure transformer ratio; check connections, wiring; check secondary voltage circuit.
- 110kV isolating switch: measure insulation resistance, measure contact resistance, check connections and wiring; Strengthen contact, check control circuit.
- 110kV SF6 circuit breaker: measure insulation resistance; measure contact resistance; measure opening and closing time; check connections, wiring; dtrengthen contact; check control circuit.
- 110kV current transformer: measure insulation resistance; measure current transformer ratio; measure error, magnetization test; mheck connections, wiring; strengthen contact; check secondary current circuit.
- 110kV earthing knife: measure insulation resistance; measure ES contact resistance; check connections, wiring; strengthen contact; industrial cleaning.
- 110kV/6.6kV, 9.6MVA power transformer: measure insulation resistance; measure transformer ratio at steps; measure DC coil resistance; measure dielectric loss angle; measure leakage current in dielectric; low-voltage excitation; check connections, wiring; strengthen contact; check oil level, oil leakage; replace silicagel (if damp)
- 9.6MVA transformer oil sample, under-load tap changer: chemical testing of 02 oil samples (chemical properties test); analysis of dissolved gas in 01 MB main tank oil sample.
- Automatic pressure regulating relay: test by characteristic value; check tap control circuit; industrial cleaning.
- Differential protection relay
- Overcurrent protection relay
- Power transformer protection relay system: test the internal protection relay; test the operation of each relay; and test the operation of the circuit breaker at both ends of the transformer.
- Grounding system: Measure ground resistance; check wire connections.
– – –
For more information about the 110kV substation maintenance service, please contact us through the information below: